LR2 THERMAL RELAY

LR2-D13 LR2-D23 LR2-D-33
32-80A
LR2-D-33
80-93A
  This series of thermal relay can be used in the circuit of 50Hz or 60Hz,rated insulation voltage 660V,rated current 0.1-93A for protecting the phase break when the electric motor is overload. The relay has diffierent mechanism and temperature compensation & can be pluged in LC1-D series AC contactor.At present,it is the most advanced thernal relay in the world.

Specifications
Type Rated working current of thermal relay Thermal component
Rated Current (A) Regular or scale of rated current(A)
LR2-D13 25 0.16 0.10-0.16
0.25 0.16-0.25
0.40 0.25-0.40
0.63 0.40-0.63
1.0 0.63-1.0
1.6 1.0-1.6
2.0 1.25-2.0
2.5 1.6-2.5
4.0 2.5-4.0
6.0 4.0-6.0
8.0 5.5-8.0
10.0 7.0-10.0
13.0 9.0-13.0
18.0 12.0-18.0
25.0 17.0-25.0
LR2-D23 36 32 23.0-32.0
36 28.0-36.0
LR2-D33 93 32 23.0-32.0
40 30.0-40.0
50 37.0-50.0
65 48.0-65.0
70 55.0-70.0
80 63.0-80.0
93 80.0-93.0

Characteristic
a.Fundamental parameter of the main circuit
(a).Rated insulation voltage 660V.
(b).Rated working current 25,36,93A seperately.
(c).The regulatorseal of rated setting current and setting.
(d).Current of the Thermal component(see list 1)
b.Auxiliary Circuit
(a).There are one pair of N/O and N/C contact with electric insulation
(b).Rated insulation Voltage 500V
(c).Ratd frequency 50-60Hz
(d).Use group,rated working voltage,appoint thermal current and ratd current

Use Group ACLL DCLL
Rated working voltage V 220 380 500 220 110
Rated working current A 4 3 2 0.1 0.22
Appointed thermal current A 5

LA7-D1064 LA7-D2064 LA7-D3064

Performance Curve
Time