LC1-D AC Contactors

.

LC1-D09 LC1-D25 LC1-D65 LC1-D115 LC1-D150
LC1-D170
  LC1-D series AC contactor is suitable for using in the circuit up to the rated voltage 660V AC 50Hz or 60Hz, rated current 95A, for making, breaking, frequent starting & controlling the AC motor. Combined with the auxiliary contact block, air delay contactor, mechanical interlocking contactor, star-deltastarter. With the thermal relay, it is combined into the electromagnetic starter. The contactor is produced according to ICE158-1, VDE0660 & BS5432.
volts(vac) 24 42 48 110 220/230 230 240 380/400 400 415 440 500 660
50Hz B5 D5 E5 F5 M5 P5 U5 Q5 V5 N5 R5 S5 Y5
60Hz B5 D6 E6 F6 M5 - U6 Q6 - - R6 - -
50/60Hz B7 D7 E7 F7 M7 P7 U7 Q7 V7 N7 R7 - -

Specificaton

Type LC1-009 LC1-012 LC1-018 LC1-025 LC1-032
Rated working current
(A)
AC3 9 12 18 25 32
AC4 3.5 5 7.7 8.5 12
AC3 capacity of phase 3
squirrel-cage motor
AC3(KW)
220V 2.2 3 4 5.5 7.5
380V 4 5.5 7.5 11 15
415V 4 5.5 9 11 15
440V 4 5.5 9 11 15
660V 5.5 7.5 10 15 18.5
Rated heat current(A) 20 20 32 40 50
electrical life AC4x10e4 20 20-15 20-7 15-7 15-7
AC3x10e6 2 2 2 2 2
Mechanical life x 10e6 20 20 20 20 20
number of the contact 3P+NO
3P+NC
Type LC1-040 LC1-050 LC1-065 LC1-080 LC1-095
Rated working current
(A)
AC3 40 50 65 80 95
AC4 18.5 24 28 37 44
AC3 capacity of phase 3
squirrel-cage motor
AC3(KW)
220V 11 15 18.5 22 25
380V 18.5 22 30 37 45
415V 22 25 37 45 45
440V 22 30 37 45 45
660V 30 33 37 45 45
Rated heat current(A) 60 80 80 125 125
electrical life AC4x10e4 10-7 7 7-6 7-5 7-5
AC3x10e6 2 2 1.6 1.6 1.6
Mechanical life x 10e6 20 20 20 10 10
number of the contact 3P+NC+NO