NFIN Residual Current Device (RCD)
|

| NFIN 2P 40A 0.03A |
NFIN 4P 63A 0.1A |
|
The
Residual Current Device(RCD) NFIN is in conformity with the standards
of IEC 1008, VDE 0664, CEE27 and BS 4293.
It can cut off the fault circuit immediately on the occasion of shock
hazard or earth leakage of trunk line.Thus it is suitable to avoid
the shock hazard and fire caused by earth leakage.
NFIN RCD is mainly suitable for using in varieties of plants, enterprises,
buildings, constructions, commerce. Hotels and families, It can be
used in circuits up to single phase 240V,threephase 415V,50 or 60Hz.
|
Specifications
| Type |
NFIN25 |
NFIN40 |
NFIN63 |
NFIN100 |
| Rated current In(A) |
25 |
40 |
63 |
100 |
| Rated operating current for
earth leakage Iждn(A) |
0.03,0.1,0.3,0.5 |
0.1
0.3
0.5 |
| Rated non-operating current
for earth leakage Iждn(A |
0.5Iждn |
| Voltage Un(V) |
240(220)
415(380) |
| Pole |
2,
4 |
Main Technical Data
| Operating time(seconds) |
Iждn |
2Iждn |
0.25A (or 5Iждn) |
| 0.2 |
0.1 |
0.04 |
Limited value of non-operating
current for balance load
or unbalance load |
2In |
In minimum value
of rated
making and breaking capacity |
In=25 |
In=40 |
In=63 |
| 200 |
300 |
400 |
Rated conditional
short
circuit current Inc(A) |
1500 |
2000 |
3000 |
| Endurance(times) |
4000 |
|
Operation Principle
|
|
|
|
|
Dimensions
 |
|