The product, applicable to protect
line-conductor and overload, and short-circuit of small sealed motors,
is mainly for protection of circuits with AC 220V and 50Hz/60Hz,
and for unfrequent conversion under normal conditions as well. Its
action can be up to two pole with its only one pole volume and be
used as a leakage breaker by assembling with leakage. It is produced
as per IEC898-87.
Technical data
1. Current rating: 1,2,3,4,6,10,16,20,25,32A
at 30¡æ£»
2. Voltage rating: 220.240V AC;
3. Breaking capacity: to EN 60.898:4500
4. Number of operating cycles(O-C): 20000
5. Tripping characteristics:
B curve: the magnetic release operate between 3 and 5 In,
C curve: the magnetic release operate between 5 and 10 In.
|